Are you looking for Air Conditioning maintenance in Arlington Heights, IL ? Our AC and Air Conditioning service technicians have years of experience working on Central AC Systems like yours in Arlington Heights, IL. has service vehicles on call that are fully equipped with the tools and parts necessary to get your Cooling System back up and operating.
We offer Central Air Conditioner maintenance and maintenance agreements to keep your AC system running great. You can rely on to advise you properly and to do excellent work promptly. Ask us about maintenance agreements for your high efficiency Air Conditioner today.
We provide Air Conditioning Maintenance in Arlington Heights, IL
We provide Air Conditioning Maintenance Agreements in Arlington Heights, IL
Get Your Quote Today
A/C Report
Clean And Check Outdoor Condenser
High Pressure - 220
Low Pressure - 109
Ambient Temp - 65
Delta T Reading -19
Contactor Resistance Reading - No Issues
Low Voltage Wiring Check No Issues
Capacitor Reading 75/10@74.9/9.87
Clean Out Electrical Compartment Clean
Refrigeration Line Check - Low Side Insulation No Issues
Service Valve Cap No Issues
Amp Draw On Compressor -22.1@12.91
Amp Draw On Condenser Fan -1.7@1.23
Lock Rotor Amps - 125@143.1 Recommended Hard Start Kit
Check Filter/Replace Replaced Air Filter Dirty
Clean Drain No Issues
Test Blower Motor No Issues
Chris, D. Arlington Heights , IL 05-26-2022
A/C Report 1st Floor
Clean And Check Outdoor Condenser
High Pressure - 215
Low Pressure - 108
Ambient Temp - 55
Delta T Reading -18
Contactor Resistance Reading - No Issues
Low Voltage Wiring Check No Issues
Capacitor Reading 45/5@44.67/4.75
Clean Out Electrical Compartment Clean
Refrigeration Line Check - Low Side Insulation Well Insulated
Service Valve Cap No Issues
Amp Draw On Compressor -15.2@6.74
Amp Draw On Condenser Fan -1.1@ .60
Lock Rotor Amps - 70@81.8 Recommended Hard Start Kit
Check Filter/Replace Air Filter Looks Good
Clean Drain No Issues
Test Blower Motor No Issues
A/C Report 2nd Floor Ac
Clean And Check Outdoor Condenser
High Pressure -
Low Pressure -
Ambient Temp - 55
Delta T Reading -17
Contactor Resistance Reading - No Issues
Low Voltage Wiring Check No Issues
Capacitor Reading 45/5@44.89/5.06
Clean Out Electrical Compartment No Issues
Refrigeration Line Check - Low Side Insulation Well Insulated
Service Valve Cap No Issues
Amp Draw On Compressor -15.2@6.89
Amp Draw On Condenser Fan -1.1@.60
Lock Rotor Amps - 70@77.8 Recommended Hard Start Kit
Check Filter/Replace Replaced Air Filter
Clean Drain No Issues
Test Blower Motor No Issues Sean , B. Arlington Heights , IL 05-27-2022
A/C Report 1st Floor
Clean And Check Outdoor Condenser
High Pressure - 195
Low Pressure - 110
Ambient Temp - 60
Delta T Reading -18
Contactor Resistance Reading - No Issues
Low Voltage Wiring Check No Issues
Capacitor Reading 40/5@39.73/4.87
Clean Out Electrical Compartment Clean
Refrigeration Line Check - Low Side Insulation Well Insulated
Service Valve Cap No Issues
Amp Draw On Compressor -15.3@6.71
Amp Draw On Condenser Fan -1.1@.74
Lock Rotor Amps - 83@81.1
Check Filter/Replace Air Filter Looks Good
Clean Drain No Issues
Test Blower Motor No Issues
A/C Report 2nd Floor
Clean And Check Outdoor Condenser
High Pressure - 195
Low Pressure - 120
Ambient Temp - 60
Delta T Reading -18
Contactor Resistance Reading - No Issues
Low Voltage Wiring Check No Issues
Capacitor Reading 40/5@39.89/5.05
Clean Out Electrical Compartment Clean
Refrigeration Line Check - Low Side Insulation Well Insulated
Service Valve Cap No Issues
Amp Draw On Compressor -15.3@6.67
Amp Draw On Condenser Fan -1.1@.76
Lock Rotor Amps - 83@85.4
Check Filter/Replace Air Filter Looks Good
Clean Drain No Issues
Test Blower Motor No Issues Kerri, B. Arlington Heights , IL 05-26-2022
Completed 2 Ac Clean And Checks And 2 Furnace Clean And Checks. Both Units Are Working Appropriately And Up To Manufacturing Specifications. During Inspection Found Dual Ran Capacitor For Outdoor Unit For Second Floor Out Of Specifications And Recommended Replacement. Homeowner Approved. Renewed Membership Agreement For Both Systems During Visit. Sean , B. Arlington Heights , IL 04-12-2024